BTU / Power Calculator
Calculate heat output and power requirements for AV equipment. Upload CSV or enter manually.
Devices
Recommendations
Results
How this is calculated
Real power W = VA × power factor. Amps inputs use A × V for single phase, or √3 × line-to-line V × A for three phase. Supply current = total VA ÷ supply V (÷ √3 for balanced three phase). Three-phase current assumes an evenly balanced load; check actual phase allocation. Circuit counts use a conservative 80% planning allowance (for example, 12.8 A on a 16 A circuit and 8 A on a 10 A circuit), commonly used for continuous loads under NEC rules; confirm local requirements. Counts refer to single-pole circuits.
1 W of heat = 3.412 BTU/hr; 1 cooling ton = 12,000 BTU/hr. Enter manufacturer thermal dissipation per unit for amplifiers, at the intended operating level. Use input watts for heat is the default; switch it off to enter separate thermal dissipation. HVAC margin adds 0% to heat load. This excludes room heat gains. A blank or zero device voltage uses the supply voltage for a matching phase connection. For a single-phase device on a balanced three-phase supply it uses line-to-line voltage ÷ √3; enter the actual device voltage when known.
Disclaimer
These tools are provided in beta and are subject to change. All calculations and results may contain errors and should be independently verified by a qualified professional before use in any design, installation, or safety-critical application. AV500 accepts no liability for decisions made based on these outputs.