AV Tools / Power & Infrastructure

BTU / Power Calculator

Calculate heat output and power requirements for AV equipment. Upload CSV or enter manually.

Projects
Pro

Devices

1 line item · 1 unit
Total W0
BTU/hr0

Recommendations

Minimum 16A circuits at 80% derating0
Minimum 10A circuits at 80% derating0

Results

@ 230V
Calculated Load0 W · 0 BTU/hr
Total power / apparent power0 W / 0 VA1 line item · 1 unit
Total heat0BTU/hr
Total current0.0 A@ 230V · single phase
Cooling0.00tons
16A circuits0
10A circuits0
Line items1

How this is calculated

Real power W = VA × power factor. Amps inputs use A × V for single phase, or √3 × line-to-line V × A for three phase. Supply current = total VA ÷ supply V (÷ √3 for balanced three phase). Three-phase current assumes an evenly balanced load; check actual phase allocation. Circuit counts use a conservative 80% planning allowance (for example, 12.8 A on a 16 A circuit and 8 A on a 10 A circuit), commonly used for continuous loads under NEC rules; confirm local requirements. Counts refer to single-pole circuits.

1 W of heat = 3.412 BTU/hr; 1 cooling ton = 12,000 BTU/hr. Enter manufacturer thermal dissipation per unit for amplifiers, at the intended operating level. Use input watts for heat is the default; switch it off to enter separate thermal dissipation. HVAC margin adds 0% to heat load. This excludes room heat gains. A blank or zero device voltage uses the supply voltage for a matching phase connection. For a single-phase device on a balanced three-phase supply it uses line-to-line voltage ÷ √3; enter the actual device voltage when known.

Disclaimer

These tools are provided in beta and are subject to change. All calculations and results may contain errors and should be independently verified by a qualified professional before use in any design, installation, or safety-critical application. AV500 accepts no liability for decisions made based on these outputs.